Thread: 4 Door Controller with IUM

  1. #1
    Banned
    Join Date
    Jan 2008
    Posts
    129
    Thanks
    8
    Thanked 17 Times in 13 Posts
    Rep Power
    0
    Reputation
    260

    Default 4 Door Controller with IUM

    I have 4 X 4DC that were installed by another company but were offline since. Now the customer wants to bring them back online. That was suppose to be the simplest thing to do given all installations and wirings were already done.
    BUT not so, 2 of the 4DC were reading Raw card data, which is right, but the other 2 were reading 26 Bit Wiegand. All 4DCs were wired and programmed in the same way and have IUMs.

    DAS said to check:
    1. Magswipe link is OFF -done
    2. Ensure D+ and D- are correct - done
    3. Hard default the 4DC - done.

    Still the same.

    Any suggestions?



Look Here ->
  • #2
    Senior Member
    Join Date
    Jan 2008
    Location
    Sydney :P~~~
    Posts
    1,051
    Thanks
    8
    Thanked 74 Times in 54 Posts
    Rep Power
    246
    Reputation
    657

    Default

    When u go into the 4DC menu on the codepad (19,28) what IUM is the system seeing?
    SIM MIUM LIUM ?

  • #3
    Banned
    Join Date
    Jan 2008
    Posts
    129
    Thanks
    8
    Thanked 17 Times in 13 Posts
    Rep Power
    0
    Reputation
    260

    Default

    Is there a menu in 19,28 that shows what the 4DC is seeing its memory? Which sub-menu is that?

  • #4
    Senior Member
    Join Date
    Jan 2008
    Location
    Sydney :P~~~
    Posts
    1,051
    Thanks
    8
    Thanked 74 Times in 54 Posts
    Rep Power
    246
    Reputation
    657

    Default

    Yep, 19 then 28 then go into the address of that DGP (4DC)
    and there is a menu (IUM) or similar and it will show SIUM MIUM or LIUM

  • #5
    Member redozqld's Avatar
    Join Date
    Aug 2008
    Location
    Here in Brisbane
    Age
    45
    Posts
    360
    Thanks
    7
    Thanked 24 Times in 18 Posts
    Rep Power
    205
    Reputation
    142

    Default Check?

    First thing I would check is to make sure that you've programmed them all the same, create a new client under (titan etc) the panel and do a full upload, check the door controllers there, make sure that they are sequentially numbered, and nothing is doubled up, default your four door (you mentioed earlier), and download the entire program back into the system, one thing to check would be to make sure the door are programmed correctly (Check menu 19-28-1 for DGP), check to make sure that menu 19-4- that the DGP's are polled and they are set for four door controller.

    Another thing to check is to make sure that the units are all running RECENT firmware, had one company a while back, wont mention any names, spend a week trying to figure out a problem with iums, found out later that they didnt upgrade the firmware on the four doors, it was a 98 firmware release...

    Happy hunting

  • #6
    Senior Member
    Join Date
    Jan 2008
    Location
    Sydney :P~~~
    Posts
    1,051
    Thanks
    8
    Thanked 74 Times in 54 Posts
    Rep Power
    246
    Reputation
    657

    Default

    Yeah, and when you do the download, dont do it from titan.
    perform the download from the codepad and watch it go through

  • #7
    Banned
    Join Date
    Jan 2008
    Posts
    129
    Thanks
    8
    Thanked 17 Times in 13 Posts
    Rep Power
    0
    Reputation
    260

    Default

    The 4DC thats not working has a 99 firmware. I checked with GE, they said its OK with IUM. Maybe I should change the firmware?

  • #8
    Senior Member
    Join Date
    Jan 2008
    Posts
    701
    Thanks
    13
    Thanked 51 Times in 40 Posts
    Rep Power
    226
    Reputation
    257

    Default

    try defaulting the door controllers first and downloading the data back into them. You'll probably find your problem will go away pretty quickly after doing this.

    I have found using this method will fix most issues like your talking about.

  • #9
    Senior Member
    Join Date
    Jan 2008
    Posts
    701
    Thanks
    13
    Thanked 51 Times in 40 Posts
    Rep Power
    226
    Reputation
    257

    Default

    forget it, just re read your psot. i do agree with Keef though do the download form the codepad.

  • #10
    Senior Member
    Join Date
    Jan 2008
    Location
    Sydney :P~~~
    Posts
    1,051
    Thanks
    8
    Thanked 74 Times in 54 Posts
    Rep Power
    246
    Reputation
    657

    Default

    Did you check via the 19,28 menu that the 4DC is recognising the IUM as the correct type/

  • #11
    Banned
    Join Date
    Jan 2008
    Posts
    129
    Thanks
    8
    Thanked 17 Times in 13 Posts
    Rep Power
    0
    Reputation
    260

    Default

    Not yet, returning later today with some 4DC firmware. Yes i had hard-defaulted the panel and done the upload/download via the codepad the last time, but did not work.

  • Similar Threads

    1. DOTL on 4 Door Controller
      By jrtech in forum Security Alarms
      Replies: 38
      Last Post: 03-11-09, 07:50 PM
    2. WTT 360 wireless controller for wired controller
      By hikaru in forum Buy Sell and Trade
      Replies: 0
      Last Post: 01-04-09, 02:29 PM
    3. Garage Door
      By DaX in forum Electronics
      Replies: 3
      Last Post: 13-08-08, 12:11 PM
    4. Garage Door Controller
      By Stimpy in forum Electronics
      Replies: 8
      Last Post: 23-07-08, 02:14 AM
    5. SM Bus controller & USB controller issues?
      By osci in forum Operating Systems
      Replies: 3
      Last Post: 04-05-08, 12:52 PM

    Bookmarks

    Posting Permissions

    • You may not post new threads
    • You may not post replies
    • You may not post attachments
    • You may not edit your posts
    •